Ring cable lug | 300mm² | M12 | crimp | T-300/12 | 010900
Code: 010900Price 12.79 € VAT incl.( 10.57 € VAT excl. )-
Ring cable lug | 300mm² | M12 | crimp | T-300/12 | 010900
T-300/12 – crimp ring cable lug 300 mm² for a copper conductor with a stud hole for an M12 bolt. Used to terminate a cable or wire end and connect it reliably to a terminal, busbar or device bolt.
Key idea:
The lug is selected by two values: conductor cross-section (300 mm²) and the size of the bolt it is connected to (M12). Large cross-section lugs are used for power cables at transformers, switch-disconnectors, busbars and incoming devices. A correctly crimped lug forms a mechanically strong, low-resistance connection.Conductor cross-section
300 mm²Stud hole
M12Connection
crimpSeries / marking
T-300/12Operating principle
Insulation is stripped from the conductor to the depth of the lug barrel and the strands are pushed fully into the barrel.
The barrel is crimped with a crimping tool using a die for 300 mm². During crimping the barrel deforms together with the conductor – a solid joint is formed without a screw contact on the strands.
The ring part with the M12 hole is bolted to the terminal or busbar, and the crimp area is insulated with heat-shrink tubing.
Why choose T-300/12?
An exact cross-section and bolt combination (300 mm² / M12) – no need to enlarge the hole or crimp a wrong-size lug, so the joint stays reliable throughout its service life.Technical specifications
Product type Crimp ring cable lug Marking / code T-300/12 / 010900 Series T Conductor cross-section 300 mm² Stud hole (bolt) M12 Conductor copper Connection method crimping Main functions
- Conductor termination – the 300 mm² conductor is secured and does not splay under the bolt.
- Crimped joint – strong mechanical and electrical connection without an extra screw on the strands.
- M12 stud hole – fits an M12 bolt or stud directly.
- T series – lugs of one type across the whole range of cross-sections and bolt sizes.
- Easy identification – cross-section and bolt size are given in the marking T-300/12.
Where is it used?
- Transformer substations and switchgear
- Switch-disconnectors and power switches
- Busbar systems
- High-power incomers
- Generator and power factor correction connections
- Industrial power circuits
Use by need
For the installing electrician.
One clear 300 mm² / M12 combination – fewer errors when building a panel.For the equipment repair technician.
A damaged or overheated lug is replaced with a product of the same size.For the designer and buyer.
The complete T series – from small to large cross-sections.Practical application
If a 300 mm² copper cable has to be connected in a panel to a busbar or device with an M12 bolt, use T-300/12: strip the insulation, push the conductor into the barrel, crimp with a 300 mm² die and insulate the joint with heat-shrink tubing.Advantages
- Exact cross-section and bolt combination
- Reliable crimped joint
- Suitable for copper conductors
- Consistent series system
- Compact ring part
Disadvantages / limitations
- Uninsulated – the crimp area must be insulated with heat-shrink tubing
- Requires a crimping tool and the correct die
- Not suitable for aluminium conductors – use bimetallic lugs
- A lug of the wrong cross-section will not form a reliable joint
Safety and installation notes
- Install only with the voltage disconnected and its absence verified
- Use a die intended for 300 mm²
- Push the conductor to the end of the barrel, leave no protruding strands
- Do not crimp several conductors in one lug unless intended
- Tighten the bolt to the torque specified by the equipment manufacturer
- After installation, check that the joint does not heat up under load
Quick selection guide
300 mm²M12crimpTfor copperSuitable when you need:- to terminate a 300 mm² copper conductor
- to connect to an M12 bolt or stud
- a durable crimped joint in a panel or device
Check before use:- whether the conductor cross-section is exactly 300 mm²
- whether the terminal bolt is M12
- whether you have the right crimping tool and die
- whether the conductor is copper (bimetallic lugs for aluminium)
Important reminder: A lug does not replace insulation of the joint – cover the crimp area with heat-shrink tubing.FAQ
How do I choose a ring lug?
By the conductor cross-section (300 mm²) and the bolt size (M12) – both must match.Is it suitable for aluminium cable?
No – bimetallic (Al/Cu) lugs are used for aluminium conductors.Which tool is used for crimping?
Crimping pliers or a hydraulic press with a 300 mm² die.Can it be fitted to a larger bolt?
No – the M12 hole is only for an M12 bolt; choose another lug for a different bolt.Does it need insulating?
Yes – the lug is uninsulated; cover the crimp area with heat-shrink tubing.What is the difference between the T and TCD series?
The TCD series is made to DIN 46235; T is another series in this group. Both are crimp lugs for copper conductors.Ring cable lug | 300mm² | M12 | crimp | T-300/12 | 010900
T-300/12 – crimp ring cable lug 300 mm² M12 for terminating copper conductors and connecting them to panels, busbars and equipment terminals.
Published: 2026-11-12 · Parameters according to the supplier's specification: 2026-11-12
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.This product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products
CYKY-J 5G16 | 5×16 mm² | Copper power cable | 0.6/1 kV | black | 1 m | NKTCode: C520218CYKY-J 5G16 (5×16 mm²) – 0.6/1 kV copper power cable for three-phase 400 V circuits with neutral. Solid cores, PVC insulation and sheath, suitable indoors, outdoors and in the ground. NKT, price per 1 m.
Price 15.00 € VAT incl.( 12.40 € VAT excl. )CYKY-L 5G10 | 5×10 mm² | Copper power cable | 450/750 V | black | 1 m | LietkabelisCode: 91951013CYKY-L 5G10 (5×10 mm²) – 450/750 V copper power cable for three-phase 400 V circuits with neutral. Solid cores, PVC insulation and sheath, suitable indoors, outdoors and in the ground. AB Lietkabelis, price per 1 m.
Price 8.67 € VAT incl.( 7.17 € VAT excl. )Aluminium power cable | 4x120mm² | AXMK | Class 2 | 1m | BlackCode: AXMK 4x120AXMK 4×120 mm² aluminium power cable designed for fixed 0.6/1 kV electrical power transmission and distribution lines. The cable features aluminium conductors, XLPE insulation, and a black UV-resistant PVC outer sheath. Suitable for installation outdoors, underground, in dry, damp and wet areas, cable ducts, conduits, and concrete. Maximum operating temperature – 90 °C.
Price 15.13 € VAT incl.( 12.50 € VAT excl. )Aluminium power cable | 4x120mm² | AXMK | Class 2 | 1000m | BlackCode: SKU#165996553256573221AXMK 4×120 mm² aluminium power cable designed for fixed 0.6/1 kV electrical power transmission and distribution lines. The cable features aluminium conductors, XLPE insulation, and a black UV-resistant PVC outer sheath. Suitable for installation outdoors, underground, in dry, damp and wet areas, cable ducts, conduits, and concrete. Maximum operating temperature – 90 °C.
Sold by the drum, i.e. the minimum order quantity is 1000 metres.
Delivery time: up to 6 weeks.
Price 11.04 € VAT incl.( 9.12 € VAT excl. )Aluminium power cable | 4x150mm² | AXMK | Class 2 | 500m | blackCode: SKU#165996595240116261Aluminium power cable AXMK 4×150 mm², designed for fixed 0.6/1 kV electrical power transmission and distribution lines. The cable features aluminium conductors, XLPE insulation, and a black PVC outer sheath resistant to UV radiation. Suitable for installation outdoors, underground, in dry, damp and wet areas, cable ducts, pipes, and concrete. Maximum operating temperature – 90 °C.
Sold by the drum, i.e. the minimum order quantity is 500 metres.
Delivery time: up to 6 weeks.
Price 14.52 € VAT incl.( 12.00 € VAT excl. )Copper installation cable NYM-J | 5×2.5 mm² | 300/500 V | white | 1 m | Lietkabelis KH05VV-U 5G2.5Code: 92052501NYM-J 5×2.5 mm² (KH05VV-U 5G2.5) – AB Lietkabelis copper installation cable with solid class 1 conductors, PVC insulation and a white PVC sheath, 300/500 V. For fixed installation inside buildings: in walls, under plaster, in conduits and trunking. Sold by the metre.
5 cores (L1, L2, L3, N, PE) for three-phase 400 V installation with neutral: three-phase sockets, cookers, sub-boards and mixed loads.
Price 2.38 € VAT incl.( 1.97 € VAT excl. )