Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 160 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs
Code: ES-2SLQ1-160A/4SaiLingsi SLQ1 4P 160 A – automatic transfer switch with single-phase voltage monitoring and separate outputs. 400 V, AC-33iB.
-
Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 160 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs
SaiLingsi SLQ1 is a panel-mounted automatic transfer switch (ATS) for two sources: main (I) and backup (II). When the main supply fails, the load is automatically transferred to the backup and returned when the main supply is restored. 4P, 160 A, 400 V, single-phase monitoring.
Key point
One unit with integrated controller, motor drive and I-0-II handle. The manufacturer states automatic return to the main source and a fire control input. Ui, Uimp, Icw and transfer time depend on the frame size.Poles / current
4P / 160 AVoltage monitoring
1 phase (230 V)Transfer
< 3–5 s (by frame)Terminals
2 inputs – 2 outputsHow it works
The controller monitors the source voltage. When main source I fails (manufacturer threshold – voltage below 85 % Ue) and backup II is energised, the motor drive transfers the contacts to II. When I returns, the switch automatically goes back to I.
A key switch selects automatic or manual mode. In manual mode positions I, 0 or II are selected with the handle; in position 0 both sources are disconnected. The handle can be padlocked.
The manufacturer specifies a fire control input – the fire alarm signal is connected to it.
Single-phase monitoring: the controller is supplied from and monitors 230 V (L–N). "2 inputs – 2 outputs" terminals: each switch module has its own output, so the outputs are joined on the load side according to the product wiring diagram.
Technical specifications
Type Automatic transfer switch (ATS) with integrated controller Manufacturer, model SaiLingsi (Wenzhou) Electronics Co., Ltd – SLQ1-160A/4 Poles 4P Rated current 160 A Operating voltage Ue AC 400 V, 50 Hz Control voltage AC 230 V Utilization category AC-33iB Class PC (manufacturer data) Insulation voltage Ui 500–800 V (by frame) Impulse voltage Uimp 6–8 kV (by frame; SLQ1-100 nameplate – 8 kV) Short-time withstand current Icw 5–16 kA (by frame) Transfer time < 3 s – 5 s (by frame) Voltage monitoring Single phase, L–N 230 V Terminal arrangement 2 inputs – 2 separate outputs Mechanical durability 9000 cycles Voltage deviation threshold < 85 % Ue Control Auto / manual (key), I-0-II handle, lockable Additional functions Automatic return, fire control input Installation category / pollution degree II / 3 Ambient temperature −5…+40 °C (24 h average ≤ +35 °C) Altitude up to 2000 m Standard GB/T 14048.11 (nameplate) Data source Manufacturer nameplate and SaiLingsi technical information ⚠ The brand on the device is SaiLingsi (Wenzhou) Electronics. The manufacturer gives Ui, Uimp, Icw and transfer time as frame ranges – check the exact value for this size on the device nameplate. The photos show SLQ1-100/4P – other sizes and 3P versions differ in appearance and dimensions.Functions
- Automatic transfer I → II and automatic return II → I
- I-0-II handle with position 0
- Auto / manual key switch
- Handle padlock
- Fire control input
- Integrated controller and motor drive
Versions and nearest sizes
- SLQ1 4P 160 A – 1-phase monitoring, 2–1
- SLQ1 4P 160 A – 3-phase monitoring, 2–1
- SLQ1 3P 160 A – 3-phase monitoring, 2–1
- SLQ1 4P 100 A – 1-phase monitoring, 2–2
- SLQ1 4P 250 A – 1-phase monitoring, 2–2
- SLQ1 4P 400 A – 1-phase monitoring, 2–2
- Single-phase monitoring – the controller monitors only L–N 230 V; three-phase monitoring – all three phases.
- 2 inputs – 1 output: common load output; 2 inputs – 2 outputs: separate outputs joined during installation.
- 4P also switches the N conductor, 3P only the phases.
Applications
- Building incoming panels with a backup generator
- Industrial, commercial and high-rise buildings
- Transfer between two grid supplies
- Sites requiring fire control
Practical example
Building with a 160 A supply and a generator: grid – I, generator – II. Both outputs are joined on the load side with a busbar according to the product wiring diagram. The controller monitors one phase.
Advantages
- Integrated controller – no separate automation needed
- Automatic return to the main source
- I-0-II handle and padlock for maintenance
- Fire control input
- 9000 mechanical cycles
Points to note
- Transfer takes up to 3–5 s (by frame)
- No generator start control specified by manufacturer
- Does not break short circuits – upstream protection required
- Only one phase monitored
- Outputs must be joined during installation
⚡ Safe installation
- Installation must be carried out by a qualified electrician with both sources disconnected.
- Install short-circuit and overload protection upstream of the ATS on both supplies.
- Select cables or busbars for 160 A and the terminal size.
- Connect a generator to the building installation only through a transfer switch.
- Make the output connections according to the product diagram – incorrect wiring may connect the sources together.
How to choose
Select a current not lower than the incoming protection current. For three-phase motors or sensitive loads choose three-phase monitoring. 4P – when N must also be switched with a generator.
4P · 160 A1 phase (230 V)2 inputs – 2 outputsAC-33iB · 400 VSuitable if:- separate outputs suit the panel design
- single-phase monitoring is sufficient
- incoming current up to 160 A
Check:- exact Ui, Uimp and Icw values on the nameplate
- short-circuit current at the installation point
- panel space – frame dimensions depend on current
Important: An ATS is not a protective device – install short-circuit and overload protection separately. If in doubt, consult a qualified electrician.Frequently asked questions
What does "2 inputs – 2 outputs" mean?
Each switch module has its own output. On the load side they are joined according to the product wiring diagram.Does the ATS start the generator?
The manufacturer does not specify a generator start function for this model – the generator start is controlled by its own automation.How long does the transfer take?
According to the manufacturer – from under 3 s to 5 s depending on the frame.Can it be switched manually?
Yes, with manual mode selected by the key, the handle is turned to I, 0 or II.What does the fire control input do?
The fire alarm signal is connected to it according to the product wiring diagram.Can you help with selection?
Yes. Send us the incoming current, network type and generator power – we will help you choose.Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 160 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs
SLQ1 4P with single-phase monitoring and separate outputs – where separate outputs suit the panel design.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.This product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products
Network plug | RJ45 connector (8P8C) | for UTP CAT 6e cable | unshielded | through-plug | transparentCode: WT117Price 0.20 € VAT incl.( 0.17 € VAT excl. )U-FTP Cable | 6A CAT | 4x2x23 AWG | shielded | copper | UV resistant | outdoor use | blackCode: KIF6AOUTS500Price 0.73 € VAT incl.( 0.60 € VAT excl. )Price 0.98 € VAT incl.( 0.81 € VAT excl. )