  • Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 630 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs

    Code: ES-2SLQ1-630A/4

    SaiLingsi SLQ1 4P 630 A – automatic transfer switch with single-phase voltage monitoring and separate outputs. 400 V, AC-33iB.

  • Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 630 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs

    SaiLingsi SLQ1 is a panel-mounted automatic transfer switch (ATS) for two sources: main (I) and backup (II). When the main supply fails, the load is automatically transferred to the backup and returned when the main supply is restored. 4P, 630 A, 400 V, single-phase monitoring.

    Key point
    One unit with integrated controller, motor drive and I-0-II handle. The manufacturer states automatic return to the main source and a fire control input. Ui, Uimp, Icw and transfer time depend on the frame size.
    Poles / current
    4P / 630 A
    Voltage monitoring
    1 phase (230 V)
    Transfer
    < 3–5 s (by frame)
    Terminals
    2 inputs – 2 outputs

    How it works

    The controller monitors the source voltage. When main source I fails (manufacturer threshold – voltage below 85 % Ue) and backup II is energised, the motor drive transfers the contacts to II. When I returns, the switch automatically goes back to I.

    A key switch selects automatic or manual mode. In manual mode positions I, 0 or II are selected with the handle; in position 0 both sources are disconnected. The handle can be padlocked.

    The manufacturer specifies a fire control input – the fire alarm signal is connected to it.

    Single-phase monitoring: the controller is supplied from and monitors 230 V (L–N). "2 inputs – 2 outputs" terminals: each switch module has its own output, so the outputs are joined on the load side according to the product wiring diagram.

    Technical specifications

    Type Automatic transfer switch (ATS) with integrated controller
    Manufacturer, model SaiLingsi (Wenzhou) Electronics Co., Ltd – SLQ1-630A/4
    Poles 4P
    Rated current 630 A
    Operating voltage Ue AC 400 V, 50 Hz
    Control voltage AC 230 V
    Utilization category AC-33iB
    Class PC (manufacturer data)
    Insulation voltage Ui 500–800 V (by frame)
    Impulse voltage Uimp 6–8 kV (by frame; SLQ1-100 nameplate – 8 kV)
    Short-time withstand current Icw 5–16 kA (by frame)
    Transfer time < 3 s – 5 s (by frame)
    Voltage monitoring Single phase, L–N 230 V
    Terminal arrangement 2 inputs – 2 separate outputs
    Mechanical durability 9000 cycles
    Voltage deviation threshold < 85 % Ue
    Control Auto / manual (key), I-0-II handle, lockable
    Additional functions Automatic return, fire control input
    Installation category / pollution degree II / 3
    Ambient temperature −5…+40 °C (24 h average ≤ +35 °C)
    Altitude up to 2000 m
    Standard GB/T 14048.11 (nameplate)
    Data source Manufacturer nameplate and SaiLingsi technical information
    ⚠ The brand on the device is SaiLingsi (Wenzhou) Electronics. The manufacturer gives Ui, Uimp, Icw and transfer time as frame ranges – check the exact value for this size on the device nameplate. The photos show SLQ1-100/4P – other sizes and 3P versions differ in appearance and dimensions.

    Functions

    • Automatic transfer I → II and automatic return II → I
    • I-0-II handle with position 0
    • Auto / manual key switch
    • Handle padlock
    • Fire control input
    • Integrated controller and motor drive

    Versions and nearest sizes

    Applications

    • Building incoming panels with a backup generator
    • Industrial, commercial and high-rise buildings
    • Transfer between two grid supplies
    • Sites requiring fire control

    Practical example

    Building with a 630 A supply and a generator: grid – I, generator – II. Both outputs are joined on the load side with a busbar according to the product wiring diagram. The controller monitors one phase.

    Advantages

    • Integrated controller – no separate automation needed
    • Automatic return to the main source
    • I-0-II handle and padlock for maintenance
    • Fire control input
    • 9000 mechanical cycles

    Points to note

    • Transfer takes up to 3–5 s (by frame)
    • No generator start control specified by manufacturer
    • Does not break short circuits – upstream protection required
    • Only one phase monitored
    • Outputs must be joined during installation

    ⚡ Safe installation

    • Installation must be carried out by a qualified electrician with both sources disconnected.
    • Install short-circuit and overload protection upstream of the ATS on both supplies.
    • Select cables or busbars for 630 A and the terminal size.
    • Connect a generator to the building installation only through a transfer switch.
    • Make the output connections according to the product diagram – incorrect wiring may connect the sources together.
    ☝ Elsprendimai.eu recommends: ATS selection guide · Diagrams: 3P or 4P · Consultation

    How to choose

    Select a current not lower than the incoming protection current. For three-phase motors or sensitive loads choose three-phase monitoring. 4P – when N must also be switched with a generator.

    4P · 630 A
    1 phase (230 V)
    2 inputs – 2 outputs
    AC-33iB · 400 V
    Suitable if:
    • separate outputs suit the panel design
    • single-phase monitoring is sufficient
    • incoming current up to 630 A
    Check:
    • exact Ui, Uimp and Icw values on the nameplate
    • short-circuit current at the installation point
    • panel space – frame dimensions depend on current
    Important: An ATS is not a protective device – install short-circuit and overload protection separately. If in doubt, consult a qualified electrician.

    Frequently asked questions

    What does "2 inputs – 2 outputs" mean?
    Each switch module has its own output. On the load side they are joined according to the product wiring diagram.
    Does the ATS start the generator?
    The manufacturer does not specify a generator start function for this model – the generator start is controlled by its own automation.
    How long does the transfer take?
    According to the manufacturer – from under 3 s to 5 s depending on the frame.
    Can it be switched manually?
    Yes, with manual mode selected by the key, the handle is turned to I, 0 or II.
    What does the fire control input do?
    The fire alarm signal is connected to it according to the product wiring diagram.
    Can you help with selection?
    Yes. Send us the incoming current, network type and generator power – we will help you choose.

    Automatic transfer switch ATS SaiLingsi SLQ1 | 4P | 630 A | 400 V | single-phase monitoring | 2 inputs – 2 outputs

    SLQ1 4P with single-phase monitoring and separate outputs – where separate outputs suit the panel design.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.