Products catalog

  • Automatic transfer switch ATS GRL DNH41 | 1P+N | 10–80 A | 230 V | voltage and current display | DIN

    Code: ESDNH41
    Price 251.63 € VAT incl.
    ( 207.96 € VAT excl. )
    Buy more, pay less
    10+ pcs.  – 94.86 € for pcs. -62%

    GRL DNH41 – single-phase automatic transfer switch 1P+N with voltage and current display, adjustable current limit 10–80 A and return delay 1–30 s. DIN mounting.

  • Automatic transfer switch ATS GRL DNH41 | 1P+N | 10–80 A | 230 V | voltage and current display | DIN

    GRL DNH41 is a single-phase automatic transfer switch (ATS) 1P+N that transfers the load to a backup source (usually a generator) when the grid fails and returns it when the grid is restored. The display shows voltage and current.

    Key point
    According to the manufacturer, grid → backup transfer takes 3 s, and the return takes place after an adjustable 1–30 s delay so the grid can stabilise. The current limit is adjustable 10–80 A – when exceeded, an overload alarm is activated.
    Poles / current
    1P+N / 10–80 A
    Voltage
    230 V AC
    Transfer
    3 s → / 1–30 s ←
    Indication
    U and I display

    How it works

    While the grid voltage is normal, the load is supplied from the grid. When the grid fails, the switch transfers to the backup source after 3 s (manufacturer data).

    When the grid returns, the load is transferred back after the set 1–30 s delay. This avoids switching during short grid fluctuations.

    The display shows voltage and current; LEDs show which source is active, whether the load is supplied and whether there is a fault. The 10–80 A current setting is used for the overload alarm.

    Technical specifications

    Type Automatic transfer switch (ATS), 1P+N
    Manufacturer, model GRL – DNH41
    Rated voltage AC 230 V
    Current setting 10–80 A (adjustable)
    Frequency 50/60 Hz
    Insulation voltage Ui AC 500 V
    Impulse voltage Uimp 1.5 kV
    Grid → backup 3 s
    Backup → grid 1–30 s (adjustable)
    Categories AC-21A (IEC 60947-3), AC-31B (IEC 60947-6-1)
    Operating voltage limits 0.75–1.15 Un
    Own consumption 4.5 VA (AC 230 V)
    Wire cross-section 16–25 mm²
    Mounting DIN rail 35 × 7.5 mm
    Protection degree IP20
    Operating temperature −5…+55 °C
    Pollution degree 2
    Data source GRL technical information and catalogue
    ⚠ Brand – GRL. The table lists only manufacturer-stated parameters; check exact data on the device nameplate and in the instructions.

    Functions

    • Automatic transfer grid → backup and back
    • Adjustable return delay 1–30 s
    • Voltage and current display
    • Overload alarm at set current 10–80 A
    • Status LEDs (source, load, fault)
    • DIN mounting

    Applications

    • Single-phase houses and homesteads with a generator
    • Small commercial sites
    • Single-phase critical circuits (heating, pumps)

    Practical example

    Homestead with a single-phase 6 kW generator and a 32 A supply: grid and generator to the DNH41 inputs, load panel to the output. The current limit is set to the generator's capability, the return delay e.g. to 10 s.

    Advantages

    • Display – voltage and current at a glance
    • Adjustable return delay
    • Overload alarm
    • Compact, DIN

    Points to note

    • Single-phase circuit only
    • Grid → backup transfer takes 3 s (load briefly unsupplied)
    • No generator start control specified by manufacturer
    • Uimp 1.5 kV – install downstream of surge protection

    ⚡ Safe installation

    • Installation must be carried out by a qualified electrician with both sources disconnected.
    • Install short-circuit and overload protection upstream of the switch on both supplies.
    • Connect a generator to the house installation only through a transfer switch – never through a socket outlet.
    • Wire cross-section – 16–25 mm² per manufacturer; select according to the load current.
    ☝ Elsprendimai.eu recommends: ATS selection guide · Diagrams: 3P or 4P · Consultation

    How to choose

    Suitable for a single-phase site up to 80 A. Set the current according to the incoming protection and generator power.

    Suitable if:
    • the site is single-phase
    • load current up to 80 A
    • you want to see voltage and current
    Check:
    • incoming protection upstream of the switch
    • wire cross-section (16–25 mm²)
    • surge protection
    Important: Always check exact parameters on the device nameplate and in the manufacturer's instructions. If in doubt, consult a qualified electrician.

    Frequently asked questions

    Does DNH41 start the generator?
    The manufacturer does not specify this function – the generator start is controlled by its own automation.
    Why is a return delay needed?
    So that the load is not returned too early after the grid comes back, before the voltage stabilises.
    Is it suitable for a three-phase site?
    No, DNH41 is 1P+N – for a single-phase circuit.
    Can you help with selection?
    Yes. Send us the network type, incoming protection and generator power – we will help you choose the right solution.

    Automatic transfer switch ATS GRL DNH41 | 1P+N | 10–80 A | 230 V | voltage and current display | DIN

    GRL DNH41 – single-phase ATS with voltage and current display, adjustable return delay and overload alarm.

    Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.
  • Alternative products

    U-FTP Cable | 6A CAT | 4x2x23 AWG | shielded | copper | UV resistant | outdoor use | black
    Code: KIF6AOUTS500

    The U/FTP cable is a high-quality four-pair data transmission cable designed for telecommunication, industrial, and outdoor network installations. This cable is 100% copper, ensuring maximum signal transmission efficiency and minimal signal attenuation.

    It is adapted for 10 Gigabit Ethernet (10GBASE-T) data transmission at speeds of up to 10,000 Mbps and provides high electromagnetic resistance, as each pair is shielded with aluminum foil. Thanks to the PE outer layer, the cable is resistant to moisture, UV radiation, and mechanical impact, making it ideal for outdoor installations. 

    Price 0.73 € VAT incl.
    ( 0.60 € VAT excl. )
    Network plug | RJ45 connector (8P8C) | for UTP CAT 6e cable | unshielded | through-plug | transparent
    Code: WT117

    This RJ45 Cat.6 UTP modular plug is a high-quality 8P8C unshielded network connector type, designed for Cat.6 UTP (Unshielded Twisted Pair) cables. The special straight-through design makes cable termination easier and more convenient, as the wires can be threaded through the plug, allowing a visual check of the wire arrangement before crimping the connector.

    Price 0.20 € VAT incl.
    ( 0.17 € VAT excl. )
    Solar PV cable | H1Z2Z2-K | 1x4 mm² | black | 1.5 kV DC | EN 50618 | Dca | IEMMEQU HAR
    Code: H1Z2Z2K

    The cable is designed for connecting photovoltaic (solar energy) systems and interconnecting solar modules. This cable offers excellent resistance to ultraviolet (UV) rays, ozone, atmospheric effects, and temperature fluctuations. A durable and flexible single-core copper cable with double insulation ensures long service life and safe use even in the most challenging outdoor conditions. Suitable for installation both indoors and outdoors.

    Price 0.98 € VAT incl.
    ( 0.81 € VAT excl. )
  • privacy policy