Replacement SPD module Type 1+2 | Iimp 7 kA | Imax 50 kA | Uc 275 V | LSP FLP7-275/0
Code: FLP7-275/0LSP FLP7-275/0 is a replacement Type 1+2 plug-in module for FLP7-275 series bases. When the indicator turns red, pull out the module and insert a new one – no rewiring, the base stays.
-
Replacement SPD module Type 1+2 | Iimp 7 kA | Imax 50 kA | Uc 275 V | LSP FLP7-275/0
LSP FLP7-275/0 is a replacement Type 1+2 plug-in module for FLP7-275 series bases. When the indicator turns red, pull out the module and insert a new one – no rewiring, the base stays.
Key point:
A spare module cuts downtime to a minute: isolate the SPD backup fuse, pull out the tripped module, insert the new one – protection is back and the rest of the board stays in service.Class
Type 1+2 / Class I+II / B+CIimp (10/350 µs)
7 kAUp
≤ 1.5 kVFits bases
FLP7-275Operating principle
The module plugs into an FLP7-275 series base (1P, 3P or 4P, with or without S contact) without tools – the connections in the base remain untouched.
Inside the module is a high-energy varistor with a thermal disconnector. The surge is diverted through the base terminals to PE or PEN.
When the varistor wears out, the thermal disconnector disconnects it, the window turns red and the S base contact changes over.
What does LSP FLP7-275/0 do for you?
LSP FLP7-275/0 restores protection within a minute: no need to buy a whole base, disconnect wires or shut down the switchboard – only the tripped module is replaced.Technical specifications
Product type Replacement SPD module Type 1+2 Manufacturer / model LSP FLP7-275/0 Class (IEC / EN 61643-11) Type 1+2 / Class I+II / B+C Poles / configuration Replacement plug-in module for FLP7-275 bases Nominal voltage Un 230 V AC Max. continuous operating voltage Uc 275 V AC Impulse current Iimp (10/350 µs) 7 kA Nominal discharge current In (8/20 µs) 20 kA Max. discharge current Imax (8/20 µs) 50 kA Voltage protection level Up ≤ 1.5 kV Remote signalling contact The signalling contact is in the base (S versions); the module fits FLP7-275/1, /3, /4 and their S bases Protective element High-energy varistor (MOV), plug-in module Standard IEC 61643-11:2011, EN 61643-11:2012 Main functions
- Iimp 7 kA (10/350 µs) – the same as the module of a new FLP7-275 base.
- Imax 50 kA (8/20 µs) – withstands strong switching impulses.
- Thermal disconnector – a worn varistor disconnects safely.
- Status window – green / red on the front of the module.
- Fits all FLP7-275 bases – 1P, 3P, 4P and S versions.
How does it differ from similar models?
- LSP FLP7-275/1 – 1P | Iimp 7 kA | Up ≤ 1.5 kV – Base this module fits.
- LSP FLP7-275/4S – 4P TN-S | Iimp 7 kA | Up ≤ 1.5 kV – Base this module fits.
- LSP FLP7-275/3S – 3P TN-C | Iimp 7 kA | Up ≤ 1.5 kV – Base this module fits.
Where is it used?
- Replacing a tripped FLP7-275 module after a storm
- Spare module at sites without permanent staff
- Scheduled SPD inspection and replacement of worn modules
- Spare stock for switchboard maintenance companies
- Spare-parts kit for panel builders
- Refurbishing SPDs without replacing the base
Selection and installation
- Pick the scheme by network type: TN-C – 3P between L and PEN, TN-S – 4P (4+0), TT – only "3+1" with an N–PE spark gap.
- With an external LPS the value depends on the lightning protection level (LPL): LPL III–IV usually needs 12.5 kA per pole, LPL I–II needs more – we will calculate it.
- Choose 5–8 kA per pole models where there is no LPS and the threat comes through an overhead line.
- Install the SPD at the incomer upstream of the RCD (or after an S-type RCD) so that the discharge current does not pass through the RCD.
- Backup fuse – within the manufacturer limit; if the incoming fuse is larger, give the SPD its own fuse (e.g. 125 A gG).
Use by need
For the site owner.
A spare module in stock – protection is restored the same day.For the electrician.
Replacement without disconnecting wires: only the SPD fuse is switched off.For the maintenance company.
One part number for all FLP7-275 bases – simpler spare stock.Practical application
If after a storm one pole's window on an FLP7-275/4S base is red, switch off the SPD backup fuse, pull out that module, insert an FLP7-275/0 and switch back on – the other modules and wires stay in place.Pros
- Fast restoration of protection
- No need to replace the base or wiring
- Fits all FLP7-275 bases
- Thermal disconnector and indication
Cons / limitations
- Fits FLP7-275 series bases only
- The signalling contact is in the base, not in the module
- Not used on its own without a base
⚡ Safety and installation notes
- Before replacing the module, switch off the SPD backup fuse or switch.
- Make sure the module type and Uc match the base (FLP7-275).
- Insert the module fully – a partly inserted module does not protect.
- After replacement, check that the windows of all poles are green.
☝ From experience- Keep the leads to the SPD and from it to PE as short as possible – total length up to 0.5 m. Every extra metre adds about 1 kV to Up and the protection loses its point.
- Run the PE conductor straight to the main earthing bar, not through other devices' terminals. In a Type 1 circuit use at least 16 mm² Cu.
- Pull out the modules or disconnect the SPD before an insulation resistance test (500–1000 V) – otherwise the tester shows "leakage" and the modules may be damaged.
- Check the indicator after every storm and at least once a year. Keep a spare module on site – replacement takes a minute: isolate only the SPD backup fuse or MCB, the rest of the board can stay in service.
- If the sub-boards are more than 10 m away or feed sensitive electronics, add a separate Type 2 or Type 3 SPD there – the incomer alone is not enough.
☝ Elsprendimai.eu recommends: It is also worth keeping spare fuses for the SPD circuit, and if the base is not yet an S version, consider the FLP7-275/4S with signalling contact.Quick selection guide
Type 1+2 / Class I+II / B+C7 kA≤ 1.5 kVFLP7-275Suitable when you need:
- To replace a tripped FLP7-275 module
- To keep a spare module on site
- To restore protection without shutting down the switchboard
Check before use:
- Base type – FLP7-275
- Which pole has tripped (red window)
- Whether the backup fuse has blown
Important reminder: The module does not replace the complete SPD – it can only be used with an FLP7-275 base.
FAQ
Does it fit the FLP12.5 base?
No, the FLP7-275/0 is intended for FLP7-275 series bases only.Does the whole switchboard need to be switched off for replacement?
No, switching off the SPD backup fuse or switch is enough.How many modules does a 4P base need?
Four, but only those with a red window are replaced.Does the module have a signalling contact?
No, the contact is in the S version base and is actuated by the module status.How do I know the module needs replacing?
The window on the front of the module turns red and the S base contact changes over.Can it be stored for a long time?
Yes, in a dry room; before installation check that the window is green.Not sure which one to choose? See the Type 1+2 SPD selection guide or contact us – we will select it from your board diagram.Documents and sources
Checked 2026-10-17.
Replacement SPD module Type 1+2 | Iimp 7 kA | Imax 50 kA | Uc 275 V | LSP FLP7-275/0
LSP FLP7-275/0 – plug-in T1+T2 module for FLP7-275 bases: Iimp 7 kA, Imax 50 kA. Protection is restored within a minute, without disconnecting wires.
Illustrative image may have been created using AI. The appearance of the product may differ slightly from the image shown. Please refer to the technical specification.This product is marked with the CE label, which confirms that it complies with all applicable European Union directives and regulations. CE marking is not just a formality – it is an important indicator of quality and safety, ensuring that the product has been properly assessed, tested, and can be safely used throughout the EU market.
CE certification means that the product has been evaluated according to the main criteria:
Safety requirements – ensures that the product does not pose a risk to the user or the environment
Electromagnetic compatibility (EMC) – the device does not interfere with other equipment and is resistant to external disturbances
Environmental standards – complies with current ecological and material usage requirements
Operational reliability – the product is suitable for long-term use according to its intended purposeCE marking allows this product to:
be legally supplied and used in all European Union countries
ensure a high level of quality and safety
be used in residential, commercial, and industrial environmentsThe CE mark is a declaration of the manufacturer’s responsibility, confirming that the product complies with all applicable standards and has been assessed according to EU legislation.
What does this mean for you as a buyer?
Safe use in everyday activities
Reliable performance and reduced risk of failure
Compliance with EU standards and requirements
Suitability for professional solutions
Love it? Share your thoughts in a review!Write Review Alternative products