Selection guide: how to choose a sensor or transmitter for an HVAC system
A fan, damper, boiler or pump cannot "see" the room – it only knows what the sensor reports. If the sensor is the wrong type, wired to the wrong input or mounted in the wrong place, even the most expensive controller is working blind: it overheats, over-ventilates or keeps cycling on and off. This guide helps you choose a sensor by answering three questions: what are we measuring, what signal does the controller accept and where will the sensor be installed. How a sensor signal becomes a fan or damper action is explained in the HVAC automation guide.
Blue – information Green – benefit to you Orange – ⚠ check Red – ⚡ safety and errors
Contents
-
What do you need? Quick selection
-
Sensor, transmitter, controller or thermostat?
-
Passive temperature sensors: PT100, PT1000, Ni1000, NTC, thermocouple
-
Signal: 0–10 V, 4–20 mA, Modbus, relay or wireless
-
How to calculate: signal, wire resistance, thermostat load
-
Where to install: room, duct, outdoors, pipe
-
⚠ What to check before buying
-
✗ Most common mistakes
-
Diagram: room sensor – wrong and right
-
FAQ
What do you need? Quick selection
|
Situation |
Solution |
Where to look |
|
Heat recovery unit or duct temperature to the controller |
A passive duct sensor of the type specified by the controller manufacturer (usually PT1000 or NTC). If the controller reads Modbus – a Modbus duct transmitter |
PT1000, 150 mm · NTC 10 kΩ · Modbus DTS-M |
|
Ventilation by occupancy – office, classroom, hall |
NDIR CO₂ sensor with 0–10 V output to the fan controller or Modbus RTU to the BMS. Room type – in the room; duct type – in the extract air duct |
Room RCMFG · Duct DSCDG3 |
|
Home air quality monitoring on your phone, without a controller |
Smart CO₂ meter with NDIR sensor and Wi-Fi (Tuya) – shows CO₂ (often temperature and humidity as well) and sends alerts |
CO₂ Wi-Fi, NDIR · all air quality meters |
|
Pool hall, bathroom, warehouse humidity – control a fan or dehumidifier |
Temperature and humidity transmitter with analogue outputs and Modbus; for simple on/off – a hygrostat with a relay contact |
Duct DSTHG · Room RSTHG · Hygrostat PHG02 |
|
Outdoor temperature and humidity (weather compensation) |
Outdoor sensor IP65, −30…+70 °C – on a north-facing wall, in a place shaded from the sun |
Outdoor ODTHM |
|
Filter clogging, fan operation monitoring |
Differential pressure switch (contact) or pressure controller with analogue output for constant pressure control |
PSW-500 with tubes · pressure switch guide |
|
Electric underfloor heating, room temperature |
16 A room thermostat with NTC floor sensor; with Wi-Fi – phone control and weekly schedule |
Wi-Fi 16 A · all thermostats |
|
Electrical enclosure: heating in winter, fan in summer |
DIN thermostats: NC contact – for the heater, NO – for the fan; both in one housing – a dual thermostat |
NC for heating · NO for cooling · Dual NO+NC |
|
Cold warehouse, garage, utility building |
Industrial mechanical thermostat IP65, 15(6) A, with internal or external sensor |
−20…+40 °C, external · −35…+20 °C |
|
Industrial process: furnace, dryer, oil |
Type K thermocouple (up to 600 °C in our range) or PT100 (−50…+450 °C) with a transmitter to 4–20 mA; for moving or inaccessible surfaces – a non-contact IR sensor |
Thermocouple K · PT100 · Transmitter AT-3I · IR sensors |
|
Water or heat transfer fluid flow in a pipe |
Without cutting the pipe – ultrasonic clamp-on; for conductive liquids and high accuracy – electromagnetic; for small flows – a low-flow meter |
Clamp-on DN25 · Electromagnetic · 50–1200 l/h |
|
Water or fuel level in a tank or borehole |
Submersible hydrostatic probe, ultrasonic or radar sensor – depending on the liquid and tank. For petrol and other flammable liquids – only Ex (ATEX) certified sensors |
Level sensor guide |
|
Compressed air, inert gases; wind and air velocity |
MEMS gas flow meter 0–100 l/min with RS485 (for flammable gases and oxygen – only dedicated, certified meters); wind speed sensor with relay output (for awnings, windows, cranes) |
Compressed air · other gases · anemometers |
What you gain by choosing correctly
-
Ventilation runs only as much as needed: CO₂ and humidity control lets you reduce airflow in empty rooms and save heating and fan energy.
-
Comfort without overheating or draughts – the controller receives the real temperature, not a distorted one.
-
The sensor fits the controller right away: no need to change the input module, program "corrections" or look for another device on site.
-
Faults are noticed in time: a clogged filter, stopped fan or broken wire is signalled, not discovered after a complaint.
Sensor, transmitter, controller or thermostat?
The same word "sensor" in product names covers four different types of device. Before buying, the key is to understand which level your need belongs to:
1. Passive sensor
Just a sensing element that changes resistance (PT1000, NTC) or generates mV (thermocouple). No power supply needed. Connected to a controller that can read that type.
2. Active transmitter
With electronics and a power supply (usually 24 V). Outputs a standard signal: 0–10 V, 4–20 mA or Modbus RTU. Suits any controller with a matching input.
3. Sensor-controller
Measures and controls by itself: regulates a fan via 0–10 V / PWM signal or switches a relay according to a set threshold. No separate controller required.
4. Thermostat / hygrostat
The simplest control: a contact switches on and off at a set threshold. For heating, enclosure ventilation, dehumidifiers – no programming.
|
Level |
Output |
When to choose |
Examples |
|
Passive |
Resistance (Ω) or mV |
The controller or heat recovery unit has an input for a specific type (e.g. "PT1000", "NTC 10k") |
Room PT1000, immersion PT1000 |
|
Active transmitter |
0–10 V, 4–20 mA, Modbus RTU |
PLC, BMS, frequency converter or controller with a universal input; long cable runs |
T+RH RSTHG, CO₂ DSCDG3 |
|
Sensor-controller |
0–10 V / PWM control, relay |
A single fan or zone, no BMS; you want "plug it in and it works" |
CO₂ RCMFG, T+RH RCTHG |
|
Thermostat / hygrostat |
Relay contact (NO, NC or changeover) |
Switching heating, a fan or a dehumidifier on/off without a controller |
Thermostat–hygrostat DIN, TEM 16 |
Passive temperature sensors: PT100, PT1000, Ni1000, NTC, thermocouple
The passive sensor type must match the controller input setting exactly. A controller expecting PT1000 will show a fault with a PT100 (100 Ω on the PT1000 scale would correspond to below −200 °C), and an NTC 10 kΩ in place of an NTC 20 kΩ gives an error that varies with temperature and typically reaches a dozen or more degrees. So always check the controller or heat recovery unit manual first – and only then choose the sensor.
|
Type |
Nominal value |
Characteristic |
Where used |
In our range |
|
PT100 |
100 Ω at 0 °C |
Almost linear, ~0.385 Ω/°C (IEC 60751) |
Industry, processes, high temperatures; 3-wire or 4-wire connection |
PT100 −50…+450 °C, duct PT100 |
|
PT500 / PT1000 |
500 / 1000 Ω at 0 °C |
Same as PT100, but with 5 / 10 times higher resistance – less influence from the wires |
HVAC controllers, heat meters, heat recovery units; 2 wires are enough for short runs |
Duct PT1000, PT500 with cable |
|
Ni1000 |
1000 Ω at 0 °C |
Nickel, steeper curve than PT; comes in different standards (e.g. DIN 43760, LG-Ni1000); types are not interchangeable – choose the one specified by the controller |
Older and some European building automation systems |
Duct Ni1000 |
|
NTC |
1.8 / 2.2 / 3 / 10 / 20 kΩ (usually specified at 25 °C) |
Non-linear, resistance decreases as temperature rises; the curve constant (B) also matters |
Heat recovery units, heat pumps, underfloor heating thermostats |
1.8 kΩ · 2.2 kΩ · 3 kΩ · 10 kΩ · 20 kΩ |
|
Thermocouple J / K |
Generates mV according to the temperature difference between the hot and cold junctions |
Widest range; requires compensating cable and an input with cold junction compensation |
Furnaces, dryers, casting, extruders |
J 0–400 °C, K 0–600 °C, surface K |
Your controller doesn't have the input you need? A PT100 → 4–20 mA transmitter converts the sensor resistance into a standard signal.
Signal: 0–10 V, 4–20 mA, Modbus, relay or wireless
|
Signal |
When to choose |
What to watch out for |
|
0–10 V |
HVAC standard: fan controllers, EC motors, damper actuators, frequency converters |
Sensitive to interference and to voltage drop in the common zero (G0) wire on long runs; 0 V can mean both minimum and a broken wire |
|
4–20 mA (0–20 mA) |
Long runs, industry, PLC |
4–20 mA has a "live zero": ~0 mA = open circuit. 0–20 mA lacks this advantage – set the range you use in the controller |
|
Modbus RTU (RS485) |
Several sensors on one line, BMS, SCADA; temperature, humidity and CO₂ transmitted together |
A single bus without stubs, 120 Ω terminators only at the ends, a unique address for each device, the same baud rate and parity |
|
PoM (Power over Modbus), RJ45 |
Sentera sensors: 24 V DC power and Modbus RTU over one cable with RJ45 connectors |
This is neither Ethernet nor PoE – do not plug it into a computer network switch or router |
|
PWM |
EC fans whose control input is pulse-width modulation |
Check the frequency and level accepted by the motor |
|
Relay contact |
Thermostats, hygrostats, pressure switches, alarms |
Contact current and load type: resistive (heater) or inductive (motor, coil) – see the calculation below |
|
Wireless (Wi-Fi, Zigbee, LoRa) |
Monitoring on a phone, smart homes, remote sites |
Signal coverage, app or hub, battery replacement; wired connection is better for critical control |
How to calculate: signal, wire resistance, thermostat load
1. Value from an analogue signal
Value = min + (signal − signal start) ÷ signal span × (max − min).
Example (4–20 mA): output configured for −30…+70 °C, controller receives 12 mA → −30 + (12 − 4) ÷ 16 × 100 = +20 °C.
Example (0–10 V): CO₂ sensor 0–2000 ppm, signal 4.5 V → 4.5 ÷ 10 × 2000 = 900 ppm.
2. Wire resistance error with a 2-wire connection
Error ≈ resistance of both conductors ÷ sensor sensitivity. PT100 sensitivity ~0.385 Ω/°C, PT1000 – ~3.85 Ω/°C.
Example: 25 m cable 2 × 0.5 mm² (copper, ~0.036 Ω/m per conductor) → 50 m × 0.036 = 1.8 Ω. PT100 will read ~+4.7 °C high, PT1000 – ~+0.5 °C. That is why PT1000 is used for longer runs, while PT100 is connected with 3 or 4 wires.
3. Can the thermostat handle the load?
The marking "16(2.5) A" means: 16 A for resistive loads (heating cable, heating element), 2.5 A for inductive loads (motor, coil, pump).
Example: 2.5 kW floor heating cable, 230 V → 2500 ÷ 230 = 10.9 A – a 16 A thermostat is suitable. A 4.5 kW cable (19.6 A) requires a contactor (AC-1 ≥ 25 A) whose coil is controlled by the thermostat; the cable and circuit breaker are sized for the full current. Connect fans or pumps through a thermostat only within its inductive current rating.
Where to install: room, duct, outdoors, pipe
|
Sensor |
Good location |
Where not to install |
|
Room temperature, CO₂, humidity |
Interior wall, ~1.5 m high, where people are present; free air circulation around it |
Next to a radiator, supply air diffuser, door or window, on an exterior wall, in direct sunlight, behind a curtain or in a cabinet |
|
Duct |
Straight duct section; probe in the middle of the duct (choose the length according to the duct diameter); after a heater or cooler – far enough for the air to mix (follow the manufacturer's instructions) |
Immediately after a heater, elbow or damper; next to the duct wall; in an uninsulated duct in a cold room |
|
Outdoor |
North or north-west wall, no lower than ~2 m, protected from sun and rain |
Above windows, ventilation openings, chimneys, a heat pump outdoor unit; in the sun |
|
Pipe (immersion / strap-on) |
Immersion – in a thermowell with thermally conductive paste; strap-on – on a cleaned pipe, insulated |
Where the liquid is stagnant (dead-end branches); without insulation on a cold pipe |
|
Differential pressure switch |
Diaphragm in a vertical plane, tubes without kinks or loops, probes in the duct before and after the filter |
On a vibrating housing, with tubes sagging downwards where condensate collects |
⚠ What to check before buying
Kibirkštis: "I bought a cheaper NTC sensor for the heat recovery unit – it looks the same. And now it shows +34 °C in the extract air…"
|
What to check |
Why |
|
Controller input type |
Passive: the exact type (PT100/PT1000/Ni1000/NTC and its nominal resistance). Active: 0–10 V, 4–20 mA or Modbus |
|
Power supply |
24 V AC or 24 V DC (some models accept DC only), 85–264 V AC or battery. Versions within the same series may differ in power supply – check the product page |
|
Measuring range |
CO₂ 0–2000 ppm is enough for rooms; for greenhouses and industry – up to 5000–10000 ppm. For temperature – with a margin, but not too wide: a narrower range gives a more accurate reading |
|
CO₂ measuring principle |
Real CO₂ is measured by an NDIR sensor. Cheap "eCO₂" meters only estimate CO₂ from VOC – they are not suitable for control |
|
Mounting type and IP |
Room (usually IP30), flush-mounted, duct (usually IP54), outdoor (IP65 or higher). For duct sensors – probe length to suit the duct |
|
Thermostat contact |
NO, NC or changeover; current for resistive and inductive loads; whether the sensor is internal or remote (floor probe, capillary) |
|
For a flow meter |
Pipe DN and material, liquid temperature (90 or 160 °C version), straight sections before and after the meter, whether the liquid is conductive (required for electromagnetic meters) |
✗ Most common mistakes
|
Mistake |
Consequence |
|
Passive sensor chosen "by appearance" rather than by the controller input |
Reading off by several to a dozen or more degrees, or a fault message; the heat recovery unit heats or defrosts at the wrong time |
|
Room sensor next to a radiator, door or in the sun |
The controller "sees" the local temperature, not the room temperature – some areas overheat, others stay cold |
|
Duct sensor immediately after the heater |
Unmixed airflow – the reading jumps, heating is regulated "in waves" |
|
0–10 V or Modbus cable run together with 230/400 V or frequency converter cables |
Interference, jumping readings, communication errors |
|
Several 24 V AC devices on one transformer, but G and G0 swapped |
Short circuit through the common signal zero – damaged sensor or controller input |
|
PoM sensor with RJ45 plugged into a computer network switch |
Devices do not work, the switch or sensor may be damaged |
|
Heating cable connected directly through the thermostat, exceeding its current rating |
Contacts and terminals overheat, the thermostat fails, there is a fire risk |
|
⚡ Working in an enclosure or on a 230 V thermostat without disconnecting the power |
Risk of electric shock; even control circuits in an enclosure are often 230 V |
⚡ Safe installation – Fazė's advice
Before connecting sensors and thermostats in an enclosure, disconnect all supply circuits and verify that no voltage is present – in enclosures, 24 V and 230 V are often on adjacent terminals. Supply low-voltage sensor circuits (24 V) only from a safety isolating transformer or power supply, and route them separately from 230/400 V cables. Earth the screen at one end only – at the controller. 230 V thermostats and heating circuits must be connected by a qualified electrician, and the heating cable circuit must be protected by a residual current device (RCD) with IΔn ≤ 30 mA.
☝ Elsprendimai.eu recommends
Diagram: room sensor – wrong and right
Kibirkštis: "Everyone in the office is wearing sweaters, yet the controller shows +25 °C and keeps the fan at minimum. The CO₂ sensor is showing some strange numbers too."
Fazė: "The sensors are fine. Let's look at where and how they are installed."
✗ WRONG
① Sensor above a radiator, next to a window that gets afternoon sun
↓
② Cable conduit in the wall not sealed – cold or warm air is drawn from it into the housing
↓
③ 0–10 V signal in the same cable trunking as 230 V lighting wires
↓
④ Two 24 V AC sensors from one transformer, G and G0 swapped on the second
✓ RIGHT
① Interior wall ~1.5 m high in the occupied zone, away from heat sources, doors and diffusers
↓
② Cable entry sealed, housing openings face the room only
↓
③ Shielded signal cable routed separately from power cables, screen earthed at the controller
↓
④ On all devices G to G, G0 to G0; signal zero common with the controller
Why – explanation by diagram number
-
①: a sensor only measures the air that touches it. Above a radiator or in the sun it reads several degrees high, so the controller reduces heating even though the room is cool. On an exterior wall it is the opposite – the sensor is cooled by the wall. CO₂ near a window or door reads too low because outdoor air mixes in there.
-
②: cable conduits in the wall connect the room with other rooms, the ceiling void or the outdoors. Air at a different temperature is drawn through them into the back of the sensor housing – the reading is constantly distorted. That is why the entry must be sealed.
-
③: 230 V wires, especially with LED drivers or frequency converters, induce interference into the low-voltage signal. On a 0–10 V line, even 0.1 V of interference equals 20 ppm CO₂ (on a 0–2000 ppm scale) or 1 °C (on a 0–100 °C scale), often more. A shielded, separately routed cable eliminates this problem.
-
④: in many 24 V AC sensors the signal zero is electrically connected to the supply G0. If G and G0 are swapped on one device, a short circuit forms through the controller's common signal zero – burning out the sensor or controller input. Follow the manufacturer's wiring diagram and keep the same polarity on all devices.
⚠ The diagram is for guidance only. Check the wiring of the sensor, controller and power supply against the manufacturer's instructions and the project design. Installation is carried out by, and is the responsibility of, a qualified electrician. UAB „Elektrotechnikos sprendimai“ accepts no liability for the connection or for possible errors.
FAQ
Kibirkštis: Can I replace a PT1000 sensor with an NTC if the controller lets me choose?
Fazė: Yes, if you set the new input type in the controller and the NTC nominal resistance and curve match one of the options the controller offers. It cannot be swapped without reprogramming – the reading would be completely wrong.
Kibirkštis: How many ppm of CO₂ in a room is already bad?
Fazė: Outdoor air is about 420 ppm. In practice, ventilation is increased when indoor CO₂ rises to ~800–1000 ppm; staying above ~1400 ppm for longer often causes fatigue and reduced concentration. The exact categories (CO₂ excess above the outdoor level) for each building use are defined by EN 16798-1 and the project design.
Kibirkštis: What is the difference between a CO₂ sensor and a VOC sensor?
Fazė: CO₂ shows how much air exhaled by people is in the room – the best indicator for occupancy-based ventilation. VOC reacts to odours, cleaning agents, paints and cooking. For an office or classroom choose CO₂; for a kitchen, gym or toilets – VOC or both.
Kibirkštis: Why does the humidity sensor in the duct after the heater show only 20 %?
Fazė: Relative humidity depends on temperature: when air is heated, it holds the same amount of water, but its relative humidity drops. To control room humidity, install the sensor in the room or in the extract air duct, not in the supply duct after the heater.
Kibirkštis: When should I choose Modbus instead of 0–10 V?
Fazė: When there are many sensors, the data goes to a BMS or SCADA, or you need several values from one sensor (temperature, humidity, CO₂). For a single fan with a simple controller, 0–10 V is quicker to connect and needs no configuration.
Kibirkštis: Why does a non-contact IR sensor read too low on shiny metal?
Fazė: An IR sensor measures the energy radiated by a surface, and shiny metal radiates little and reflects its surroundings (low emissivity). Set the emissivity according to the material or measure through a matt coating, and check that the measuring spot is not larger than the object.
Sources: technical data from elsprendimai.eu product pages (Sentera Controls, Taxnele, F&F, Ouman, Honeywell, Fantini Cosmi and others); IEC 60751 (platinum resistance thermometers); IEC 60584 (thermocouples); IEC 60381-1 (4–20 mA signals); TIA/EIA-485-A (RS485); EN 16798-1 (indoor environment); Sentera Controls documentation (Power over Modbus). Checked 2026-10-17.
Send us your controller model – we will select the right sensors