Product Catalog
- Security and Surveillance Systems | accessories
- Lighting solutions for industrial | commercial | residential | outdoor environments | accessories
- Automation and Control Systems
- Smart Automated Products | Control | Transmission | Detection
-
Electrical distribution and installation
- Reactive Power Compensation Devices
- Electrical power | power cables | wires with copper conductors
- Electrical Distribution Panels, Boxes & Accessories
- Modular equipment installed in electrical distribution boxes | panels
- Smart electrical network analyzers
- Reliable power management | stabilization | control | uninterrupted supply
- Fuse holder blocks
- Fuse disconnectors
- Fuses
- Electrical installation components
- Electric current transformers
- For domestic | professional use Extension cords | power supply extensions
- Industrial | domestic socket outlets | plugs | adapters for electricity supply
- High Voltage Equipment | Components 6kV | 10kV | 12kV | 20kV
- Underground Power Transmission | Overhead Power Lines
- Surge Protection and Lightning Protection
- Solar Energy Generation and Management Equipment
- HVAC control solutions for heating and ventilation
- Accessories for cars
- Workplace Safety | Electrical Safety Equipment | LOTO
- Technical maintenance | service equipment | fire protection solutions
- Emergency safety | hygiene | sanitary solutions
- Other products
- Quality used products
Smart electrical network analyzers
-

Not sure which power analyser you need – Wi-Fi, Modbus or power quality? The selection guide gives you a 30-second table, five solution levels, measurement duration recommendations and diagrams. For a one-off measurement – analyser rental for 7 or 14 days or on demand. -
Read more
Power analyser guide: display, monitoring, Modbus or power quality
This guide gives you quick selection by task, five solution levels from a simple panel display to a portable power quality analyser, and seven selection rules. It also contains a matrix of all products in the group, analyser rental terms, a checklist, wrong-connection diagrams and practical questions and answers. The group includes panel analysers with current transformers (CTs), modular DIN analysers with Modbus, smart Wi-Fi analysers, multi-channel energy analysers, Rogowski analysers, fixed and portable power quality analysers, the D105 pulse analyser with sensors, and communication accessories. Exact parameters are given in each product description.
Colour key: ■ information · ■ benefit, solution · ■ ⚠ check · ■ ⚡ safety, mistakes
Contents: In 30 seconds · Solution levels · What do you need? · How it works · Selection rules · Measurement duration · Selection matrix · Rental · What to check · Mistakes · Wrong connections · Faults and fixes · FAQ · Related guides · Sources☝ ELSprendimai recommends: selection in 30 seconds →
Know what you want to measure? The table shows the analyser type and suitable products straight away.Selection in 30 seconds: which analyser you need
Find the row that matches your task. The second column gives the analyser type, the third shows suitable products in this group.
Task Analyser type What to choose in the group See current, voltage, power and kWh on the panel door Panel analyser with a CT kit 3 × 100 A · 3 × 200 A · 3 × 400 A · 3 × 1000 A kits; for existing X/5 A CTs – 5 A input, IP54 Monitoring a home, farm or solar plant on your phone Smart Wi-Fi analyser with CTs three-phase 100 A, Wi-Fi · 19 channels, 200 A · 16 channels, Tuya Sub-metering of an incomer or feeder with Modbus Panel or DIN analyser, class 0.5S, RS-485 96×96 mm, class 0.5S, THD · DIN, direct up to 65 A · class 0.5, for PV systems Sub-metering of dozens of circuits in a building (BMS, SCADA) Multi-channel energy analyser up to 96 single-phase / 32 three-phase circuits · with logging, class 0.5S · DIN data concentrator High currents, wide busbars, no disconnection possible Analyser with Rogowski coils 1000 A, Wi-Fi · 2000 A, Wi-Fi · panel unit with Rogowski, 3.5" display Harmonics, voltage dips, flicker – continuous monitoring Fixed power quality analyser class 0.2S, IEC 61000-4-30, IEC 61850 · DIN, Rogowski, events · class 0.2, logging One-off audit, fault finding at several sites Portable analyser with clamps or Rogowski coils portable, 4" display · power quality, Rogowski · with 500 A clamps, 10" display; for a single measurement – rental Water and gas meters, temperature, environment – together with electricity D105 pulse analyser with sensors D105 + temperature, water and gas, weather sensors No internet or Wi-Fi on site 4G communication module Modbus → 4G module · 4G module for DIN analyser · 4G USB modem for up to 5 devices Rule: first decide what the data is for: to see it (display), to monitor remotely (Wi-Fi, 4G), to feed a system (Modbus) or to investigate power quality problems (harmonics, dips). Current measurement usually requires CTs or Rogowski coils – their selection is covered in the current transformer guide.Solution levels: from a panel display to a power quality audit
Each level adds more data, communication and analysis. Choose the lowest level that answers your question.
Level 1. Panel display
You need to see current, voltage and kWh on site.- panel analyser with 3 CTs in the kit
- no communication, or RS-485 for the future
Level 2. Smart monitoring
Home, farm, solar plant, small workshop.- Wi-Fi analyser with an app
- generation and consumption in both directions
Level 3. Modbus metering
Company, building, BMS or SCADA system.- class 0.5S analyser or multi-channel
- RS-485 or Modbus TCP to the controller
Level 4. Fixed power quality
Harmonics, dips, sensitive equipment, disputes with the supplier.- IEC 61000-4-30 analyser
- event and waveform recording
Level 5. Portable audit
Contractor, energy engineer, fault finding at several sites.- portable analyser with Rogowski coils or clamps
- one-week recording, report
What do you need? Quick selection
Situation Solution Where to look Planning a compensation cabinet, need a P and cos φ profile 7–14-day three-phase recording; an analyser measuring P, cos φ and kWh is sufficient Rental, compensation guide Increasing the permitted capacity or changing the incomer protection Actual per-phase load profile over a week Rental or Wi-Fi analyser Solar inverter trips due to high voltage Voltage recording during generation and energy in both directions Wi-Fi analyser, PV analyser Flickering lighting, failing electronics, neutral overheating Power quality analyser: THD, dips, flicker, neutral current DIN power quality analyser, portable Energy costs need to be allocated to tenants or workshops Multi-channel analyser or several Modbus analysers Multi-channel, with logging Billing metering, invoices for tenants Verified (MID) electricity meter; an analyser – for sub-metering only Electricity meters Monitoring water, gas and temperature as well Pulse analyser with sensors in the same system D105, accessories How it works: what an analyser measures
An analyser measures voltage (directly or via voltage transformers) and current (directly, via a CT or a Rogowski coil) at the same time. From these it calculates active P, reactive Q and apparent S power, cos φ, energy in kWh and kvarh, and the more advanced models also harmonics, unbalance, voltage dips and flicker.
Current input5 A · 1 A · RogowskiDirect up to ~65 A, via X/5 A or X/1 A CTs, kit CTs with mA or 333 mV output, Rogowski coils.Energy accuracyclass 1 · 0.5S · 0.2SPer IEC 62053: 0.5S – sub-metering, 0.2S – incomers and power quality.CommunicationRS-485 · TCP · Wi-Fi · 4GModbus RTU / TCP for systems, Wi-Fi and cloud for monitoring, 4G – where there is no internet.Power qualityTHD · dips · flickerHarmonics up to the 50th–64th order, event recording; methodology – IEC 61000-4-30.Feature Wi-Fi analyser Panel / DIN Modbus Power quality analyser Portable Main purpose monitoring on your phone sub-metering, BMS continuous power quality audits, fault finding Measured quantities U, I, P, cos φ, kWh (often without Q and THD) U, I, P, Q, S, cos φ, kWh, kvarh, often THD all + harmonics, events, waveform all + harmonics, events Data storage in the cloud via a controller or SCADA internal memory, SD SD or internal memory Current sensors CTs in the kit X/5 A, X/1 A CTs CTs or Rogowski coils clamps or Rogowski coils Installation DIN rail in the panel panel door 96×96 mm or DIN DIN or panel door temporary, without disconnection ⚡ Safety. The analyser voltage circuits are connected via protection (fuses or a circuit breaker), and the CT secondary circuit must never be opened while current flows – use a test terminal block. Connect the voltage terminals of a portable analyser only with probes of the appropriate category (CAT III / CAT IV) and personal protective equipment.Selection rules: 7 steps
1. Purpose
Display, monitoring, sub-metering or power quality – price and functions depend on it. Billing metering (invoicing) requires an MID-verified meter, not an analyser.2. Current input and sensors
Direct connection is suitable only for low currents (e.g. up to 65 A). For higher currents – X/5 A or X/1 A CTs, kit CTs with mA / 333 mV output, or Rogowski coils. The analyser input must match the sensor output – see the current transformer guide.3. Network type and voltage
A three-phase 4-wire 230/400 V network is the most common. A medium-voltage incomer needs an analyser with a 57.7/100 V input and voltage transformers. Also check the auxiliary supply voltage (85–265 V AC, 24 V DC, etc.).4. Accuracy class
For energy – per IEC 62053-21/22: class 1 – monitoring, 0.5S – sub-metering, 0.2S – incomers and power quality measurements. Remember: the overall error also depends on the CT class.5. Communication
RS-485 Modbus RTU – reliable wired link to a controller; Modbus TCP / Ethernet – straight to the network; Wi-Fi – cloud monitoring (usually 2.4 GHz only); 4G – for remote sites; IEC 61850 – for substation automation.6. Logging and analysis
Whether data needs to be stored in the analyser (SD, internal memory), how many harmonic orders, and whether events and waveforms should be recorded. Wi-Fi analysers often do not measure Q and THD – check the product description.7. Installation and channels
Panel door cut-out 96×96 mm, DIN rail modules, portable housing. For several circuits, a multi-channel analyser is cheaper than separate instruments.Measurement duration: how long to measure?
The measurement duration depends on the question. Too short a recording misses weekend, night-time and rare events; EN 50160 assesses voltage characteristics over a week.
Goal Recommended duration What to look at Calculating compensation power 7–14 days P and cos φ on working days and at weekends Changing the permitted capacity or incomer protection 7 days (14 preferred) highest 15-min average power, phase currents Voltage quality per EN 50160 7 days 10-min averages, ±10 % Un for 95 % of the time, THD, flicker Rare fault, tripping 14 days or longer events: dips, swells, interruptions Voltage rise from a solar plant sunny days, 7–14 days voltage during generation, energy in both directions Tip: if you are measuring for a single decision only (e.g. compensation power), there is no need to buy an analyser – 7- or 14-day rental is cheaper, and the resulting profile is suitable for the calculation in the compensation guide.Selection matrix: all products in the group
Choose a situation – the matching rows will be highlighted:
AllPanel displayWi-Fi monitoringModbus / BMSMany circuitsRogowski / high currentsPower qualityPortable auditSensors and communicationProduct Type Key data When to choose Note Panel analysers with CTs 3×50 · 100 · 150 · 200 · 400 · 600 · 800 · 1000 A three-phase panel unit + 3 CTs U, I, P, kWh; CTs in the kit panel door display use only the CTs supplied in the kit 3×250 A, RS-485 three-phase panel unit + 3 CTs Modbus RTU display with the option to connect to a system 10 mA–5.5 A input · 5 A, IP54 · 50 mA, IP54 multifunction panel unit 85–440 V AC existing CTs in the panel IP54 – for damp rooms 96×96 mm, class 0.5S panel analyser and meter 57.7–480 V; via …/5 A CTs; THD up to 63rd harm.; RS-485 incomer sub-metering class 0.5, PV three-phase panel unit RS-485 Modbus solar plants, inverter control 220 V AC · 3-in-1 RJ45 · CT 1 A / 5 A · 12–24 V DC panel power analyser 6 tariffs; RS-485 Modbus Rogowski or CTs, with a choice of supply input type – per version 3.5" display multifunction panel unit Rogowski support; Modbus TCP / RS-485 incomers with high currents class 0.2S, IEC 61850 power quality analyser IEC 61000-4-30; harmonics and interharmonics up to 63rd; 2× Ethernet, 2× RS-485 switchgear, incomers, power quality disputes also 57.7/100 V input Modular DIN analysers Siemens SENTRON modular three-phase direct up to 65 A; 276/480 V circuits without CTs with CTs, RS-485 · 300 A, Wi-Fi + Modbus modular three-phase Modbus RTU sub-metering in the panel multi-channel, class 0.5S multi-channel three-phase data logging; RS-485 several circuits in one panel data concentrator multi-channel 85–240 V AC; RS-485 circuit metering for a BMS up to 96 / 32 circuits multi-channel class 0.5; IoT, BMS, SCADA buildings, shopping centres check the CT type waveform, 3.5" · events, Modbus TCP DIN power quality Rogowski; harmonics up to 50th–51st continuous power quality monitoring class 0.2 three-phase power analyser logging; harmonics; RS-485 / Modbus TCP precise incomer measurements Smart Wi-Fi analysers 1-ph, 100 A · 1-ph, 100 A, v2 single-phase Wi-Fi CTs in the kit; cloud flat, single-phase incomer 2.4 GHz Wi-Fi 3-ph, 100 A · v2 · 300 A · 600 A three-phase Wi-Fi U, I, P, cos φ, kWh in both directions homes, farms, solar plants does not measure Q and THD 1000 A · 2000 A three-phase Wi-Fi with Rogowski flexible coils in the kit high currents without disconnection 19 channels, 200 A · 300 A · 16 channels, Tuya multi-channel Wi-Fi individual circuits; bidirectional kWh homes with a solar plant, group monitoring accuracy ±2 % Portable analysers 4" display · Rogowski, SD · Rogowski, battery portable multifunction THD up to 51st harm.; logging electricians’ audits, fault finding 3.5", 32 GB · 8" touchscreen portable power quality analyser harmonics up to 50th–51st; events comprehensive power quality audit 25 A · 500 A · 2000 A clamps three-phase power quality analyser 4 U + 4 I; 0–900 V; harmonics up to 64th; 10" display professional power quality measurements clamps – by current power quality meter · 3000 A, clamps portable three-phase harmonic analysis; data logging energy engineers’ audits Pulse analyser, sensors and communication D105, internal antenna · D105, external antenna pulse analyser 2 pulse inputs; 1-Wire; 0.1–18 V; RS-485; Wi-Fi water, gas and heat meters, sensors temperature, humidity, CO₂ · wind, solar · pressure, flow, level, pH D105 sensors 1-Wire, analogue, RS-485 environmental and process monitoring compatibility – with D105 Wi-Fi antenna 3 m · 4G USB modem communication accessories Wi-Fi through a metal cabinet; 4G for up to 5 devices weak signal, no internet Modbus → 4G · 4G module DIN industrial 4G module Modbus TCP / RTU; RJ45 remote sites, SCADA All products in the group – analysers, accessories, pulse analysers and communication accessories. The MCA PLUS II single-phase analyser for compensation cabinets is in the compensation equipment group.
Analyser rental: when you only need to measure once
If measurements are needed for a single decision, buying an analyser does not pay off – we offer power analyser rental.
Duration When it fits 7 days weekly load profile – working days and weekend, disturbance finding 14 days more reliable statistics, rarely recurring events, variable production cycle On demand longer or non-standard measurements – the period is agreed individually - before increasing the permitted capacity or changing the incomer protection – actual load profile;
- before reactive power compensation – cos φ and active power profile;
- unexplained tripping, flickering lighting, equipment failures – per-phase voltage;
- phase load balancing and energy cost analysis;
- solar plant: the inverter trips due to excessive voltage.
⚠ Rental instrument – a three-phase Wi-Fi analyser (up to 100 A per phase): measures U, I, P, cos φ and energy in both directions, data sent to the cloud every 5 s, stored for up to 12 days if the connection drops. The site needs 2.4 GHz Wi-Fi at the panel. It does not measure reactive and apparent power, harmonics or short voltage transients – such questions require a power quality analyser.⚠ What to check before buying
- What exactly you need to see: kWh, cos φ, harmonics or events – not all analysers measure Q and THD.
- The current input: direct, 5 A, 1 A, mA, 333 mV or Rogowski – and whether CTs are included in the kit.
- The highest current and the CT ratio – see the current transformer guide.
- The network voltage and the analyser supply: 230/400 V, 57.7/100 V, 24 V DC.
- Communication: RS-485, Modbus TCP, Wi-Fi (2.4 GHz) or 4G – and whether the signal will reach the panel.
- Whether data is stored in the instrument itself or only in the cloud / system.
- The installation point: panel door cut-out 96×96 mm or DIN modules.
- For billing metering – an MID-verified meter, not an analyser.
✗ The most common mistakes
Mistake Consequence and how to avoid it CT ratio not entered in the analyser Readings several hundred times too low. Enter it in the settings, e.g. 400/5. CT and voltage phases do not match Wrong P and cos φ, even though the currents are correct. CT on L1 – to I1, voltage L1 – to U1. Reversed CT orientation Negative power, or export instead of import. P1 – towards the supply side. RS-485 wired as a “star” without termination resistors Communication errors, lost data. Daisy-chain topology, 120 Ω at both ends. Wi-Fi analyser inside a closed metal cabinet No connection. External antenna or 4G module. Wi-Fi analyser bought to look for harmonics Many Wi-Fi models do not measure THD. Choose a power quality analyser. Measurement too short 1–2 days do not show the weekend and rare events. Measure for at least 7 days. Analyser used for billing tenants In a dispute, its readings have no legal force. For billing metering – an MID meter. Wrong connections: wrong and correct
⚠ The diagrams are illustrative. They are not wiring diagrams. Connection must be carried out by a certified electrician according to the design and the instrument manufacturer’s instructions. UAB „Elektrotechnikos sprendimai“ accepts no liability for the connection or installation of equipment.1. CT and voltage phase matching
Diagram. The analyser calculates power by multiplying the voltage and current of the same phase. If the L1 CT is connected to the I2 input, voltage and current do not “match”: the phase angle is wrong, so power and cos φ are incorrect, even though the currents are displayed correctly.
2. RS-485 Modbus bus
Diagram. RS-485 is a linear bus: devices are daisy-chained with a single cable (twisted pair, shielded), and 120 Ω termination resistors are fitted at both ends. “Star“ branches cause signal reflections and communication errors. Each device must have a unique address.
3. Wi-Fi in a metal cabinet
Diagram. A closed metal cabinet almost completely blocks the Wi-Fi signal. Routing an external antenna above the cabinet or using a 4G module makes the connection stable.
Faults and fixes: symptom → cause → what to do
Symptom Likely cause What to do Current reads several hundred times too low CT ratio not entered Enter the CT primary and secondary current in the settings Negative power on one phase CT reversed or S1/S2 swapped Check the CT orientation and leads of that phase cos φ makes no sense, power too low CT and voltage phases mixed up Check matching L1–I1–U1, and so on Modbus data drops out or jumps No termination resistors, “star” topology, duplicate addresses, different baud rates Daisy chain, 120 Ω at the ends, unique addresses, same baud rate and parity Wi-Fi analyser frequently disconnects Weak signal in the cabinet or a 5 GHz network External antenna, 2.4 GHz network or 4G modem No THD or dip data The instrument does not measure them Choose a power quality analyser or rental Frequently asked questions
Kibirkštis asks – a young, curious electrician who dares to ask what others won’t. Fazė answers – an experienced engineer.
Kibirkštis
How does an analyser differ from an electricity meter?
Fazė
A meter records energy and, if MID-verified, is suitable for billing. An analyser measures much more – power, cos φ, phase current balance, often harmonics and events – but it is used for billing only if it has the required verification.
Kibirkštis
What analyser do I need to calculate compensation power?
Fazė
A three-phase analyser measuring P and cos φ and a 7–14-day recording are sufficient. If the site has many frequency inverters, THD is also needed. Calculation – in the compensation guide.
Kibirkštis
Is a Wi-Fi analyser suitable for a business?
Fazė
For monitoring – yes, especially at smaller sites. But if the data has to go to a BMS or SCADA, you need Modbus, and for harmonics – a power quality analyser.
Kibirkštis
Do I need CTs if the analyser comes “with current transformers”?
Fazė
No – the CTs in the kit are matched to the instrument, so use them. Other CTs cannot be connected if their output (mA, mV) does not match.
Kibirkštis
How long should I measure?
Fazė
At least a week, so that you see working days and the weekend. For rare faults or variable production – 14 days or longer.
Kibirkštis
What does IEC 61000-4-30 mean?
Fazė
It is the standard for power quality measurement methods: how to measure voltage, harmonics, dips and flicker so that results from different instruments are comparable. For disputes with the grid operator, Class A instruments are suitable.
Kibirkštis
Can I connect an analyser without short-circuiting the CT?
Fazė
Not if the CT is already working with another instrument and the line is under load. First short-circuit the secondary circuit at the test terminal block. For temporary measurements, it is simpler to use a portable analyser with clamps or Rogowski coils.Related guides
The analyser will also need current sensors, protection and space in the panel – these guides will help you choose them:- Current transformer and Rogowski coil guide – ratio, accuracy class, burden (VA) and type
- Reactive power compensation guide – how to turn measurement results into kvar
- Panel and enclosure selection guide – space for the analyser and CTs
- Surge protection device guide – protection of measuring instruments
- Phase monitoring relay guide – phase sequence and phase loss monitoring
- All product selection guides
Sources
Standards and manufacturer data used in this guide.
- IEC 61557-12 – Power metering and monitoring devices (PMD)
- IEC 62053-21 / -22 – Electricity meter accuracy classes (1, 0.5S, 0.2S)
- IEC 61000-4-30 – Power quality measurement methods; IEC 61000-4-7 – harmonics; IEC 61000-4-15 – flicker
- EN 50160 – Voltage characteristics of electricity supplied by public networks
- Directive 2014/32/EU (MID) – measuring instruments for billing metering
- Modbus over Serial Line specification – RS-485 bus, termination resistors (modbus.org)
- Manufacturer technical data in the product descriptions
Published: 2026-11-04 · Data checked against manufacturer specifications: 2026-11-04
Disclaimer. This guide, its diagrams and recommendations are for information only – they are not a design, wiring diagram or installation instructions. Analysers must be selected, connected and commissioned by a qualified, certified electrical professional in accordance with the design, the manufacturer’s instructions and applicable legislation. UAB „Elektrotechnikos sprendimai“ accepts no liability for the selection, connection, installation or operation of equipment based on this guide, or for any resulting damage.